47
SV01M
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
Sequencer: Time
units/scaling
0 0 0.1 {sec} 6553.5 Setup units/scaling for all sequencer time
related parameters
1 1 {sec} 65535
2 1 {min} 65535
NOTE:
P708 rescales the following sequencer related parameters:
- Segment Times in current step: P712, P717, P722, P727, P732, P737, P742, P747,
P752, P757, P762, P767, P772, P777, P782, P787, P792
- Sequence diagnostic/status: P561, P562
Segment #1
Segment #1
Frequency Setpoint
0.0 -500.0 {Hz} 500.0 If P112 = 1, negative sign forces reverse
direction
1
Segment #1
Accel/Decel Time
20.0 0.0 {sec} 3600.0
Segment #1
Time in current step
0.0
0
0.0 {P708} 6553.5
0 {P708} 65535
Scaling/units depend on P708
Skip segment if time = 0
Segment #1
Digital Output State
0
Value set in P713 0 1 2 3 4 5 6 7
Relay (Bit 0) 0 1 0 1 0 1 0 1
TB14 (Bit 1) 0 0 1 1 0 0 1 1
I/O option Relay (Bit 2)
0 0 0 0 1 1 1 1
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
Segment #1 TB30
Analog Output
Value
0.00 0.00 {VDC} 10.00 TB30 configuration parameter must be set to
accept this value: P150 = 10
Segment #2
Segment #2
Frequency Setpoint
0.0 -500.0 {Hz} 500.0 If P112 = 1, negative sign forces reverse
direction
Segment #2
Accel/Decel Time
20.0 0.0 {sec} 3600.0
7
Segment #2
Time in current step
0.0
0
0.0 {P708} 6553.5
0 {P708} 65535
Scaling/units depend on P708
Skip segment if time = 0
Segment #2
Digital Output State
0
Value set in P718 0 1 2 3 4 5 6 7
Relay (Bit 0) 0 1 0 1 0 1 0 1
TB14 (Bit 1) 0 0 1 1 0 0 1 1
I/O option Relay (Bit 2)
0 0 0 0 1 1 1 1
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
Segment #2 TB30
Analog Output
Value
0.00 0.00 {VDC} 10.00 TB30 configuration parameter must be set to
accept this value: P150 = 10